power meter PM710 – basic readings, THD + min/max + RS485
| range of product | PowerLogic PM700 | 
|---|---|
| device short name | PM710 | 
| product or component type | Power meter | 
| power quality analysis | Total harmonic distortion | 
|---|---|
| type of measurement | Current Voltage Frequency Power factor total Apparent power total Active power total Reactive power total Apparent power per phase Active power per phase Reactive power per phase Energy | 
| supply voltage | 125…250 V DC 115…415 V AC 45…65 Hz | 
| network frequency | 45…65 Hz | 
| maximum power consumption in VA | 5 VA | 
| display type | Backlit LCD | 
| display resolution | 6 lines | 
| sampling rate | 32 samples/cycle | 
| measurement current | 5 A 1 A | 
| input type | Current 0.005…6 A (impedance <= 0.1 Ohm) | 
| measurement voltage | 10…480 V AC 45…65 Hz phase to phase 10…277 V AC 45…65 Hz phase to neutral | 
| measurement accuracy | Power 1 % Current 0.5 % 1…6 A Voltage 0.5 % 50…227 V Frequency 0.02 Hz 45…65 Hz Power factor 0.0034 1A to 6A and from -0.5 to +0.5 | 
| accuracy class | Class 2 reactive energy conforming to IEC 62053-23 Class 1 active energy conforming to IEC 62053-21 | 
| communication port protocol | Modbus 19.2 kbauds | 
| communication port support | RS485 | 
| data recording | Min/max of instantaneous values | 
| electromagnetic compatibility | Limits for harmonic current emissions: , conforming to IEC 61000-3-2 Conducted and radiated emissions: , conforming to EN 55011 class B Electrostatic discharge immunity test: , class III, conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields: , class III, conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test: , class III, conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test: , class III, conforming to IEC 61000-4-5 Conducted RF disturbances: , class III, conforming to IEC 61000-4-6 Immunity to impulse waves: , class III, conforming to IEC 61000-4-8 Immunity to microbreaks and voltage drops: , class III, conforming to IEC 61000-4-11 Limitation of voltage changes, voltage fluctuations and flicker in low-voltage: , conforming to IEC 61000-3-3 | 
|---|---|
| mounting mode | Flush-mounted | 
| mounting support | Panel | 
| type of installation | Indoor installation | 
| overvoltage category | III | 
| IP degree of protection | IP30 back: conforming to IEC 60529 IP52 front face: conforming to IEC 60529 | 
| relative humidity | 95 % at 50 °C | 
| pollution degree | 2 | 
| ambient air temperature for operation | -5…50 °C | 
| ambient air temperature for storage | -40…85 °C | 
| operating altitude | 0…3000 m | 
| standards | IEC 61010-1 UL 508 CSA C22.2 No 14 | 
| product certifications | CE cULus | 
| width | 96 mm | 
| depth | 69 mm | 
| height | 96 mm | 
| product weight | 0.37 kg | 
| Package 1 Weight | 0.524 kg | 
|---|---|
| Package 1 Height | 1.600 dm | 
| Package 1 width | 1.500 dm | 
| Package 1 Length | 1.600 dm | 
| Sustainable offer status | Green Premium product | 
|---|---|
| EU RoHS Directive | Compliant EU RoHS Declaration | 