Description
Description
RANGE OF PRODUCT | PowerLogic PM700 |
---|---|
DEVICE SHORT NAME | PM750 |
PRODUCT OR COMPONENT TYPE | Power meter |
POWER QUALITY ANALYSIS | Total harmonic distortion |
---|---|
TYPE OF MEASUREMENT | Current Voltage Frequency Power factor total Apparent power total Active power total Reactive power total Apparent power per phase Active power per phase Reactive power per phase Energy |
SUPPLY VOLTAGE | 125…250 V DC 115…415 V AC 45…65 Hz |
NETWORK FREQUENCY | 45…65 Hz |
MAXIMUM POWER CONSUMPTION IN VA | 5 VA |
DISPLAY TYPE | Backlit LCD |
DISPLAY RESOLUTION | 6 lines |
SAMPLING RATE | 32 samples/cycle |
MEASUREMENT CURRENT | 5 A 1 A |
INPUT TYPE | Current 0.005…6 A (impedance <= 0.1 Ohm) |
MEASUREMENT VOLTAGE | 10…480 V AC 45…65 Hz phase to phase 10…277 V AC 45…65 Hz phase to neutral |
NUMBER OF INPUTS | 2 digital |
MEASUREMENT ACCURACY | Frequency 0.02 Hz 45…65 Hz Power factor 0.0034 1A to 6A and from -0.5 to +0.5 Current 0.4 % 1…6 A Voltage 0.3 % 50…227 V Power 0.5 % |
ACCURACY CLASS | Class 2 reactive energy conforming to IEC 62053-23 Class 0.5S active energy conforming to IEC 62053-22 Class 0.5 active energy conforming to ANSI C12.20 |
NUMBER OF OUTPUTS | 1 digital (static) |
COMMUNICATION PORT PROTOCOL | Modbus 19.2 kbauds |
COMMUNICATION PORT SUPPORT | RS485 |
DATA RECORDING | Alarms Min/max of instantaneous values |
ELECTROMAGNETIC COMPATIBILITY | Limits for harmonic current emissions: , conforming to IEC 61000-3-2 Conducted and radiated emissions: , conforming to EN 55011 class B Electrostatic discharge immunity test: , class III, conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields: , class III, conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test: , class III, conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test: , class III, conforming to IEC 61000-4-5 Conducted RF disturbances: , class III, conforming to IEC 61000-4-6 Immunity to impulse waves: , class III, conforming to IEC 61000-4-8 Immunity to microbreaks and voltage drops: , class III, conforming to IEC 61000-4-11 Limitation of voltage changes, voltage fluctuations and flicker in low-voltage: , conforming to IEC 61000-3-3 |
---|---|
MOUNTING MODE | Flush-mounted |
MOUNTING SUPPORT | Panel |
TYPE OF INSTALLATION | Indoor installation |
OVERVOLTAGE CATEGORY | III |
IP DEGREE OF PROTECTION | IP30 back: conforming to IEC 60529 IP52 front face: conforming to IEC 60529 |
RELATIVE HUMIDITY | 95 % at 50 °C |
POLLUTION DEGREE | 2 |
AMBIENT AIR TEMPERATURE FOR OPERATION | -5…50 °C |
AMBIENT AIR TEMPERATURE FOR STORAGE | -40…85 °C |
OPERATING ALTITUDE | 0…3000 m |
STANDARDS | IEC 61010-1 CSA C22.2 No 14 UL 508 |
PRODUCT CERTIFICATIONS | CE cULus |
WIDTH | 96 mm |
DEPTH | 69 mm |
HEIGHT | 96 mm |
NET WEIGHT | 0.37 kg |