| range of product | Modicon X80 |
|---|---|
| product or component type | Discrete input module |
| discrete input number | 64 |
| discrete input type | Isolated |
| input type | Current sink (logic positive) |
| discrete input voltage | 24 V DC, discrete input logic: positive |
| discrete input current | 0.6 mA |
| Sensor power supply | 19…30 V |
|---|---|
| input impedance | 40000 Ohm |
| insulation resistance | > 10 MOhm 500 V DC |
| power dissipation in W | 4.3 W |
| DC typical response time | 4 ms |
| DC maximum response time | 7 ms |
| paralleling of inputs | No |
| typical current consumption | 160 mA at 3.3 V DC |
| MTBF reliability | 342216 H |
| protection type | 1 external fuse per group of channel0.5 A fast blow without reverse polarity protection |
| voltage detection threshold | < 14 V DC sensor fault > 18 V DC sensor OK |
| status LED | 1 LED (green) +32 channels indicator 1 LED (green) module operating (RUN) 1 LED per channel (green) channel diagnostic 1 LED (red) module error (ERR) 1 LED (red) module I/O |
| net weight | 0.145 kg |
| IP degree of protection | IP20 |
|---|---|
| directives | 2014/35/EU – low voltage directive 2014/30/EU – electromagnetic compatibility |
| dielectric strength | 1500 V AC at 50/60 Hz 1 minute, primary/secondary 500 V DC 1 minute, between group of channels |
| vibration resistance | 3 gn |
| shock resistance | 30 gn |
| ambient air temperature for storage | -40…85 °C |
| ambient air temperature for operation | 0…60 °C |
| relative humidity | 5…95 % at 55 °C without condensation |
| operating altitude | 0…2000 m 2000…5000 m with derating factor |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Weight | 190.0 g |
| Package 1 Height | 5.481 cm |
| Package 1 width | 11.199 cm |
| Package 1 Length | 11.666 cm |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 15 |
| Package 2 Weight | 3.481 kg |
| Package 2 Height | 15.0 cm |
| Package 2 width | 30.0 cm |