Sale!

BMXCPS3500

Original price was: $ 302.00.Current price is: $ 233.00.

In stock

Category:

Description

Description

Main
RANGE OF PRODUCT Modicon X80
PRODUCT OR COMPONENT TYPE Power supply module
BACKPLANE COMPATIBILITY Not compatible with BMEXBP..02
PRIMARY VOLTAGE 100…240 V
SUPPLY CIRCUIT TYPE AC
SECONDARY POWER 15 W 3.3 V DC I/O module logic power supply
31.2 W 24 V DC I/O module power supply and processor
21.6 W 24 V DC sensor power supply
Complementary
PRIMARY VOLTAGE LIMIT 85…264 V
NETWORK FREQUENCY 50/60 Hz
NETWORK FREQUENCY LIMITS 47…63 Hz
APPARENT POWER 0.07 kVA
INPUT CURRENT 0.52 A 240 V
1.04 A 115 V
INRUSH CURRENT 30 A 120 V
60 A 240 V
I²T ON ACTIVATION 1 A².s 120 V
3 A².s 240 V
IT ON ACTIVATION 0.05 A.s 120 V
0.07 A.s 240 V
PROTECTION TYPE Internal fuse not accessible for primary circuit
Overload protection for secondary circuit
Overvoltage protection for secondary circuit
Short-circuit protection for secondary circuit
CURRENT AT SECONDARY VOLTAGE 0.9 A 24 V DC sensor power supply
1.3 A 24 V DC I/O module power supply and processor
4.5 A 3.3 V DC I/O module logic power supply
MAXIMUM POWER DISSIPATION IN W 8.5 W
STATUS LED 1 LED (green) rack voltage OK
1 LED (green) sensor voltage
CONTROL TYPE RESET push-button cold restart
ELECTRICAL CONNECTION 1 connector 2 pin(s)alarm relay
1 connector 5 pin(s)line supply, protective earth, 24 V DC input sensor
INSULATION RESISTANCE >= 100 MOhm primary/ground
>= 100 MOhm primary/secondary
NET WEIGHT 0.36 kg
Environment
IMMUNITY TO MICROBREAKS 1 ms
DIELECTRIC STRENGTH 1500 V primary/secondary I/O module logic power supply
1500 V primary/secondary I/O module power supply and processor
2300 V primary/secondary sensor power supply
1500 V primary/ground
500 V 24 V sensor output/ground
VIBRATION RESISTANCE 3 gn
SHOCK RESISTANCE 30 gn
IP DEGREE OF PROTECTION IP20
DIRECTIVES 2014/35/EU – low voltage directive
2014/30/EU – electromagnetic compatibility
AMBIENT AIR TEMPERATURE FOR STORAGE -40…85 °C
AMBIENT AIR TEMPERATURE FOR OPERATION 0…60 °C
RELATIVE HUMIDITY 5…95 % at 55 °C without condensation
PROTECTIVE TREATMENT TC
OPERATING ALTITUDE 0…2000 m
2000…5000 m with derating factor
Packing Units
UNIT TYPE OF PACKAGE 1 PCE
NUMBER OF UNITS IN PACKAGE 1 1
PACKAGE 1 HEIGHT 13.263 cm
PACKAGE 1 WIDTH 15.407 cm
PACKAGE 1 LENGTH 15.59 cm
PACKAGE 1 WEIGHT 489.8 g
UNIT TYPE OF PACKAGE 2 S04
NUMBER OF UNITS IN PACKAGE 2 12
PACKAGE 2 HEIGHT 30.0 cm
PACKAGE 2 WIDTH 40.0 cm
PACKAGE 2 LENGTH 60.0 cm
PACKAGE 2 WEIGHT 7.0 kg