Main
RANGE OF PRODUCT
Modicon X80
PRODUCT OR COMPONENT TYPE
Power supply module
BACKPLANE COMPATIBILITY
Not compatible with BMEXBP..02
PRIMARY VOLTAGE
100…240 V
SUPPLY CIRCUIT TYPE
AC
SECONDARY POWER
10.8 W 24 V DC sensor power supply
16.8 W 24 V DC I/O module power supply and processor
8.3 W 3.3 V DC I/O module logic power supply
Complementary
PRIMARY VOLTAGE LIMIT
85…264 V
NETWORK FREQUENCY
50/60 Hz
NETWORK FREQUENCY LIMITS
47…63 Hz
APPARENT POWER
0.07 kVA
INPUT CURRENT
0.31 A 240 V
0.61 A 115 V
INRUSH CURRENT
30 A 120 V
60 A 240 V
I²T ON ACTIVATION
12 A².s 240 V
IT ON ACTIVATION
0.06 A.s 240 V
0.03 A.s 120 V
PROTECTION TYPE
Internal fuse not accessible primary circuit
Overload protection secondary circuit
Overvoltage protection secondary circuit
Short-circuit protection secondary circuit
CURRENT AT SECONDARY VOLTAGE
0.45 A 24 V DC sensor power supply
0.7 A 24 V DC I/O module power supply and processor
2.5 A 3.3 V DC I/O module logic power supply
POWER DISSIPATION IN W
<= 8.5 W
STATUS LED
1 LED green rack voltage OK
1 LED green sensor voltage
CONTROL TYPE
RESET push-button cold restart
ELECTRICAL CONNECTION
1 connector 2 pin(s) alarm relay
1 connector 5 pin(s) line supply, protective earth, 24 V DC input sensor
INSULATION RESISTANCE
>= 100 MOhm primary/ground
>= 100 MOhm primary/secondary
PRODUCT WEIGHT
0.66 lb(US) (0.3 kg)
Environment
IMMUNITY TO MICROBREAKS
1 ms
DIELECTRIC STRENGTH
1500 V primary/ground
1500 V primary/secondary I/O module logic power supply
1500 V primary/secondary I/O module power supply and processor
2300 V primary/secondary sensor power supply
500 V 24 V sensor output/ground
VIBRATION RESISTANCE
3 gn
SHOCK RESISTANCE
30 gn
IP DEGREE OF PROTECTION
IP20
DIRECTIVES
2014/30/EU – electromagnetic compatibility
2014/35/EU – low voltage directive
2012/19/EU – WEEE directive
PRODUCT CERTIFICATIONS
CSA
CE
Merchant Navy
UL
RCM
EAC
STANDARDS
EN 61000-6-4
EN 61010-2-201
EN 61131-2
EN 61000-6-2
AMBIENT AIR TEMPERATURE FOR STORAGE
-40…185 °F (-40…85 °C)
AMBIENT AIR TEMPERATURE FOR OPERATION
32…140 °F (0…60 °C)
RELATIVE HUMIDITY
5…95 % without condensation 131 °F (55 °C)
PROTECTIVE TREATMENT
TC
OPERATING ALTITUDE
0…6561.68 ft (0…2000 m)
2000…5000 m (with derating factor)