ATS48C32Q

$ 1,825.00

soft starter for asynchronous motor, ATS48, 285 A, 230..415 V, 75..250 KW

Out of stock

Category: Tag:

Description

soft starter for asynchronous motor, ATS48, 285 A, 230..415 V, 75..250 KW

Main
range of product Altistart 48
product or component type Soft starter
product destination Asynchronous motors
product specific application Heavy duty industry and pumps
device short name ATS48
power supply voltage 230…415 V – 15…10 %
motor power kW 75 kW at 230 V connection in the motor supply line for severe applications
90 kW at 230 V connection in the motor supply line for standard applications
132 kW at 230 V connection to the motor delta terminals for severe applications
132 kW at 400 V connection in the motor supply line for severe applications
160 kW at 230 V connection to the motor delta terminals for standard applications
160 kW at 400 V connection in the motor supply line for standard applications
220 kW at 400 V connection to the motor delta terminals for severe applications
250 kW at 400 V connection to the motor delta terminals for standard applications
power dissipation in W 695 W for severe applications
902 W for standard applications
utilisation category AC-53A
type of start Start with torque control (current limited to 5 In)
Icl nominal current 320 A for connection in the motor supply line for severe applications
320 A for connection in the motor supply line for standard applications
554 A for connection to the motor delta terminals for severe applications
554 A for connection to the motor delta terminals for standard applications
Complementary
assembly style With heat sink
function available External bypass (optional)
power supply frequency 50…60 Hz – 5…5 %
power supply frequency limits 47.5…63 Hz
device connection In the motor supply line
To the motor delta terminals
discrete output number 2
discrete output type (LO1) logic output 0 V common configurable
(LO2) logic output 0 V common configurable
(R1) relay outputs fault relay NO
(R2) relay outputs end of starting relay NO
(R3) relay outputs motor powered NO
output absolute accuracy precision +/- 5 %
minimum switching current 10 mA at 6 V DC for relay outputs
maximum switching current Logic output 0.2 A at 30 V DC
Relay outputs 1.8 A at 230 V AC inductive load, cos phi = 0.5 20 ms
Relay outputs 1.8 A at 30 V DC inductive load, cos phi = 0.5 20 ms
discrete input number 5
discrete input type PTC, 750 Ohm at 25 °C
(Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm
discrete input voltage 24 V <= 30 V
discrete input logic Positive logic Stop, Run, LI3, LI4 at State 0: < 5 V and <= 2 mA at State 1: > 11 V, >= 5 mA
starting current 0.4…1.3 Icl adjustable
analogue output type Current output AO: 0-20 mA or 4-20 mA, impedance <500 Ohm
communication port protocol Modbus
connector type 1 RJ45
communication data link Serial
physical interface RS485 multidrop
transmission rate 4800, 9600 or 19200 bps
max nodes number 31
protection type Phase failure: line
Thermal protection: motor
Thermal protection: starter
marking CE
operating position Vertical +/- 10 degree
height 380 mm
width 320 mm
depth 265 mm
product weight 18.2 kg
Motor power range AC-3 55…100 kW at 200…240 V 3 phases
110…220 kW at 380…440 V 3 phases
110…220 kW at 200…240 V 3 phases
250…500 kW at 380…440 V 3 phases
motor starter type Soft starter
Environment
electromagnetic compatibility Conducted and radiated emissions level A conforming to IEC 60947-4-2
Damped oscillating waves level 3 conforming to IEC 61000-4-12
Electrostatic discharge level 3 conforming to IEC 61000-4-2
Immunity to electrical transients level 4 conforming to IEC 61000-4-4
Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
Voltage/current impulse level 3 conforming to IEC 61000-4-5
standards EN/IEC 60947-4-2
product certifications C-Tick
CCC
DNV
SEPRO
NOM 117
CSA
TCF
GOST
UL
noise level 54 dB
relative humidity 0…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
ambient air temperature for operation 40…60 °C (with current derating of 2 % per °C)
-10…40 °C (without derating)
ambient air temperature for storage -25…70 °C
operating altitude <= 1000 m without derating
> 1000…2000 m with current derating of 2.2 % per additional 100 m
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Weight 20 kg
Package 1 Height 42.5 cm
Package 1 width 46 cm
Package 1 Length 51 cm
Unit Type of Package 2 S06
Number of Units in Package 2 1
Package 2 Weight 33 kg
Package 2 Height 73.5 cm
Package 2 width 60 cm
Package 2 Length 80 cm
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)

EU RoHS Declaration

Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov