Description
Description
RANGE OF PRODUCT | Altistart 22 |
---|---|
PRODUCT OR COMPONENT TYPE | Soft starter |
PRODUCT DESTINATION | Asynchronous motors |
PRODUCT SPECIFIC APPLICATION | Pumps and fans |
COMPONENT NAME | ATS22 |
PHASE | 3 phase |
[US] RATED SUPPLY VOLTAGE | 208…600 V – 15…10 % |
MAXIMUM HORSE POWER RATING | 100 hp 575 V 30 hp 208 V 40 hp 230 V 75 hp 460 V |
FACTORY SETTING CURRENT | 96 A |
POWER DISSIPATION IN W | 73 W for standard applications |
UTILISATION CATEGORY | AC-53A |
TYPE OF START | Start with torque control (current limited to 3.5 In) |
ICL STARTER RATING | 110 A connection in the motor supply line for standard applications |
IP DEGREE OF PROTECTION | IP20 |
ASSEMBLY STYLE | With heat sink |
---|---|
FUNCTION AVAILABLE | Internal bypass |
SUPPLY VOLTAGE LIMITS | 177…660 V |
SUPPLY FREQUENCY | 50…60 Hz – 10…10 % |
NETWORK FREQUENCY | 45…66 Hz |
DEVICE CONNECTION | In the motor supply line |
[UC] CONTROL CIRCUIT VOLTAGE | 110 V – 15…10 % 50/60 Hz |
CONTROL CIRCUIT CONSUMPTION | 20 W |
DISCRETE OUTPUT NUMBER | 2 |
DISCRETE OUTPUT TYPE | Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O |
MINIMUM SWITCHING CURRENT | 100 mA 12 V DC relay outputs) |
MAXIMUM SWITCHING CURRENT | 5 A 250 V AC resistive 1 relay outputs 5 A 30 V DC resistive 1 relay outputs 2 A 250 V AC inductive 0.4 20 ms relay outputs 2 A 30 V DC inductive 7 ms relay outputs |
DISCRETE INPUT NUMBER | 3 |
DISCRETE INPUT TYPE | LI1, LI2, LI3) logic, 5 mA 20 kOhm |
DISCRETE INPUT VOLTAGE | 110 V <= 121 V |
DISCRETE INPUT LOGIC | Positive logic LI1, LI2, LI3 < 20 V <= 15 mA > 79 V, <= 2 mA |
OUTPUT CURRENT | 0.4…1 Icl adjustable |
PTC PROBE INPUT | 750 Ohm |
COMMUNICATION PORT PROTOCOL | Modbus |
CONNECTOR TYPE | 1 RJ45 |
COMMUNICATION DATA LINK | Serial |
PHYSICAL INTERFACE | RS485 multidrop |
TRANSMISSION RATE | 4800, 9600 or 19200 bps |
INSTALLED DEVICE | 31 |
PROTECTION TYPE | Phase failure line Thermal protection motor Thermal protection starter |
MARKING | CE |
TYPE OF COOLING | Forced convection |
OPERATING POSITION | Vertical +/- 10 degree |
HEIGHT | 14.02 in (356 mm) |
WIDTH | 5.91 in (150 mm) |
DEPTH | 9.04 in (229.5 mm) |
NET WEIGHT | 39.68 lb(US) (18 kg) |
ELECTROMAGNETIC COMPATIBILITY | Conducted and radiated emissions level A IEC 60947-4-2 Damped oscillating waves level 3 IEC 61000-4-12 Electrostatic discharge level 3 IEC 61000-4-2 Immunity to electrical transients level 4 IEC 61000-4-4 Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3 Voltage/current impulse level 3 IEC 61000-4-5 |
---|---|
STANDARDS | EN/IEC 60947-4-2 |
PRODUCT CERTIFICATIONS | CSA UL C-tick GOST CCC |
VIBRATION RESISTANCE | 1 gn 13…200 Hz)EN/IEC 60068-2-6 1.5 mm 2…13 Hz)EN/IEC 60068-2-6 |
SHOCK RESISTANCE | 15 gn 11 ms EN/IEC 60068-2-27 |
NOISE LEVEL | 56 dB |
POLLUTION DEGREE | Level 2 IEC 60664-1 |
RELATIVE HUMIDITY | 0…95 % without condensation or dripping water EN/IEC 60068-2-3 |
AMBIENT AIR TEMPERATURE FOR OPERATION | 14…104 °F (-10…40 °C) without derating) 104…140 °F (40…60 °C) with current derating 2.2 % per °C) |
AMBIENT AIR TEMPERATURE FOR STORAGE | -13…158 °F (-25…70 °C) |
OPERATING ALTITUDE | <= 3280.84 ft (1000 m) without derating > 3280.84…< 6561.68 ft (> 1000…< 2000 m) with current derating of 2.2 % per additional 100 m |
CATEGORY | 22576-ATS22 ALTISTART |
---|---|
DISCOUNT SCHEDULE | CP1G |
GTIN | 3606480167430 |
RETURNABILITY | Yes |
COUNTRY OF ORIGIN | ID |
UNIT TYPE OF PACKAGE 1 | PCE |
---|---|
NUMBER OF UNITS IN PACKAGE 1 | 1 |
PACKAGE 1 HEIGHT | 10.04 in (25.5 cm) |
PACKAGE 1 WIDTH | 12.99 in (33.0 cm) |
PACKAGE 1 LENGTH | 16.54 in (42.0 cm) |
PACKAGE 1 WEIGHT | 28.70 lb(US) (13.018 kg) |
UNIT TYPE OF PACKAGE 2 | P06 |
NUMBER OF UNITS IN PACKAGE 2 | 4 |
PACKAGE 2 HEIGHT | 29.53 in (75.0 cm) |
PACKAGE 2 WIDTH | 31.50 in (80.0 cm) |
PACKAGE 2 LENGTH | 23.62 in (60.0 cm) |
PACKAGE 2 WEIGHT | 143.46 lb(US) (65.072 kg) |