Description
Description
RANGE | PowerPact |
---|---|
PRODUCT NAME | PowerPact B |
DEVICE SHORT NAME | BJ 110 |
PRODUCT OR COMPONENT TYPE | Circuit breaker |
DEVICE APPLICATION | Distribution |
LINE RATED CURRENT | 110 A |
---|---|
NUMBER OF POLES | 2P |
CONTROL TYPE | Toggle |
BREAKING CAPACITY CODE | J |
BREAKING CAPACITY | 100 kA 208Y/120 V AC 50/60 Hz UL 489 100 kA 240 V AC 50/60 Hz UL 489 65 kA 480/277 V AC 50/60 Hz UL 489 65 kA 480 V AC 50/60 Hz UL 489 25 kA 600Y/347 V AC 50/60 Hz UL 489 50 kA 250 V DC UL 489 |
[UE] RATED OPERATIONAL VOLTAGE | 690 V AC 50/60 Hz UL 489 |
NETWORK FREQUENCY | 50/60 Hz |
[ICS] RATED SERVICE BREAKING CAPACITY | 100 kA 220…240 V AC 50/60 Hz IEC 60947-2 25 kA 500…525 V AC 50/60 Hz IEC 60947-2 10 kA 690 V AC 50/60 Hz IEC 60947-2 65 kA 380…415 V AC 50/60 Hz IEC 60947-2 65 kA 440 V AC 50/60 Hz IEC 60947-2 |
[UIMP] RATED IMPULSE WITHSTAND VOLTAGE | 8 kV IEC 60947-2 |
TRIP UNIT TECHNOLOGY | Thermal-magnetic |
CONTINUOUS CURRENT RATING | 80 % |
[UI] RATED INSULATION VOLTAGE | 800 V IEC 60947-2 |
SUITABILITY FOR ISOLATION | Yes IEC 60947-2 |
UTILISATION CATEGORY | Category A |
MECHANICAL DURABILITY | 20000 cycles IEC 947-1 Annex K ed 5.2 |
ELECTRICAL DURABILITY | 10000 cycles IEC 947-1 Annex K ed 5.2 440 V In |
CONNECTION PITCH | 1.06 in (27 mm) |
AWG GAUGE | AWG 14…AWG 2/0 aluminium/copper |
LOCAL SIGNALLING | Presence of auxiliary contacts flag green) |
MOUNTING MODE | I-Line |
ELECTRICAL CONNECTION | I-Line connection line Lugs load |
MOUNTING HEIGHT | 3.00 in (76.2 mm) |
TIGHTENING TORQUE | 31.86…38.94 lbf.in (3.6…4.4 N.m) 0.00…0.01 in² (2.5…6 mm²) (AWG 14…AWG 10) 44.25…54.87 lbf.in (5…6.2 N.m) 0.02…0.11 in² (10…70 mm²) (AWG 8…AWG 2/0) |
NUMBER OF SLOTS | 1 auxiliary switch OF plug-in) 1 voltage release MN or MX plug-in) |
POWER WIRE STRIPPING LENGTH | 0.79 in (20 mm) |
COLOR | Gray RAL 7016) |
9 MM PITCHES | 6 |
HEIGHT | 5.39 in (137 mm) |
WIDTH | 2.13 in (54 mm) |
DEPTH | 3.50 in (89 mm) |
NET WEIGHT | 2.10 lb(US) (0.952 kg) |
QUANTITY PER SET | Set of 1 |
PHASE CONNECTION | CA |
CIRCUIT BREAKER APPLICATION | HACR rated |
QUALITY LABELS | CE |
---|---|
STANDARDS | NMX J-266 GB 14048.2 CSA C22.2 No 5 UL 489 EN/IEC 60947-2 NEMA AB1 EN/IEC 60947-5-1 |
PRODUCT CERTIFICATIONS | UL IEC CCC EAC CSA NOM |
IP DEGREE OF PROTECTION | Front cover IP40 IEC 60529 |
IK DEGREE OF PROTECTION | IK07 IEC 62262 |
POLLUTION DEGREE | 3 IEC 60947-1 |
AMBIENT AIR TEMPERATURE FOR OPERATION | -13…158 °F (-25…70 °C) |
AMBIENT AIR TEMPERATURE FOR STORAGE | -58…185 °F (-50…85 °C) |
OPERATING ALTITUDE | < 6561.68 ft (2000 m) without derating 5000 m with derating |
CATEGORY | 01135 – BJA/BKA I-LINE BREAKER |
---|---|
DISCOUNT SCHEDULE | DE2 |
RETURNABILITY | Yes |
COUNTRY OF ORIGIN | US |
UNIT TYPE OF PACKAGE 1 | PCE |
---|---|
NUMBER OF UNITS IN PACKAGE 1 | 1 |
PACKAGE 1 HEIGHT | 5.39 in (13.7 cm) |
PACKAGE 1 WIDTH | 2.13 in (5.4 cm) |
PACKAGE 1 LENGTH | 3.50 in (8.9 cm) |
PACKAGE 1 WEIGHT | 2.90 lb(US) (1.315 kg) |