Description
Description
| RANGE OF PRODUCT | Modicon Quantum automation platform |
|---|---|
| PRODUCT OR COMPONENT TYPE | Safety dc discrete output module |
| DISCRETE OUTPUT NUMBER | 16 |
|---|---|
| GROUP OF CHANNELS | 1 |
| DISCRETE OUTPUT LOGIC | Positive logic (source) |
| ADDRESSING REQUIREMENT | 4 output words 7 input words |
| DISCRETE OUTPUT VOLTAGE | 19.2…30 V DC |
| ABSOLUTE MAXIMUM OUTPUT | 34 V |
| MAXIMUM VOLTAGE DROP | <0.3 V 0.5 A |
| SENSOR POWER SUPPLY | 19.2…30 V |
| MAXIMUM LOAD CURRENT | <= 0.65 A each point <= 10.04 A each group |
| SURGE CURRENT | 2 A for 10 ms |
| RESPONSE TIME | <= 20 ms at state 0 to state 1 <= 20 ms at state 1 to state 0 |
| MAXIMUM LEAKAGE CURRENT | 0.5 mA 30 V |
| PROTECTION TYPE | With |
| LOAD INDUCTANCE | Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz))) 0.5 8 Hz |
| FAULT INDICATION | Channel fault Overload Power supply fault System fault |
| ASSOCIATED FUSE RATING | 10 A |
| ISOLATION BETWEEN CHANNELS AND BUS | 1500 Vrms for 1 minute |
| ISOLATION BETWEEN GROUP AND BUS | 1500 Vrms for 1 minute |
| POWER DISSIPATION | 1.9 W + 0.65 I² |
| MARKING | CE |
| LOCAL SIGNALLING | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) 16 LEDs (green) for output status 16 LEDs (red) for system failure, diagnostic of internal channel fault |
| BUS CURRENT REQUIREMENT | 350 mA |
| PRODUCT CERTIFICATIONS | TÜV Rheinland (SIL2) CSA CSA HazLoc UL C-Tick |
|---|
| UNIT TYPE OF PACKAGE 1 | PCE |
|---|---|
| NUMBER OF UNITS IN PACKAGE 1 | 1 |
| PACKAGE 1 WEIGHT | 500.0 g |
| PACKAGE 1 HEIGHT | 4.7 cm |
| PACKAGE 1 WIDTH | 16.3 cm |
| PACKAGE 1 LENGTH | 31.3 cm |
| UNIT TYPE OF PACKAGE 2 | S03 |
| NUMBER OF UNITS IN PACKAGE 2 | 7 |
| PACKAGE 2 WEIGHT | 3.88 kg |
| PACKAGE 2 HEIGHT | 30 cm |
| PACKAGE 2 WIDTH | 30 cm |
| PACKAGE 2 LENGTH | 40 cm |