Description
Description
| RANGE OF PRODUCT | Modicon Quantum automation platform |
|---|---|
| PRODUCT OR COMPONENT TYPE | Low voltage dc discrete input modules |
| DISCRETE INPUT NUMBER | 96 |
| GROUP OF CHANNELS | 6 |
|---|---|
| LOGIC INPUT | Positive (sink) |
| DISCRETE INPUT VOLTAGE | 24 V DC |
| INPUT VOLTAGE LIMITS | 19.2…30 V |
| VOLTAGE STATE 1 GUARANTEED | 15…30 V DC |
| VOLTAGE STATE 0 GUARANTEED | 5 V DC |
| CURRENT STATE 1 GUARANTEED | >= 2.5 mA |
| CURRENT STATE 0 GUARANTEED | >= 0.7 mA |
| ADDRESSING REQUIREMENT | 6 words |
| INPUT IMPEDANCE | 6700 Ohm |
| ABSOLUTE MAXIMUM INPUT | 30 V continuous 50 V decaying pulse |
| RESPONSE TIME | <= 2 ms from state 0 to state 1 <= 3 ms from state 1 to state 0 |
| POWER DISSIPATION | 1.35 W + (0.13 x number of points on) |
| ISOLATION BETWEEN GROUP | 500 Vrms for 1 minute |
| LOCAL SIGNALLING | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) 96 LEDs (green) for input status |
| MARKING | CE |
| BUS CURRENT REQUIREMENT | 270 mA |
| MODULE FORMAT | Standard |
| NET WEIGHT | 0.3 kg |
| STANDARDS | CSA C22.2 No 142 UL 508 |
|---|---|
| PRODUCT CERTIFICATIONS | FM Class 1 Division 2 C-Tick |
| RESISTANCE TO ELECTROSTATIC DISCHARGE | 4 kV contact conforming to IEC 801-2 8 kV on air conforming to IEC 801-2 |
| RESISTANCE TO ELECTROMAGNETIC FIELDS | 10 V/m 80…2000 MHz conforming to IEC 801-3 |
| AMBIENT AIR TEMPERATURE FOR OPERATION | 0…60 °C |
| AMBIENT AIR TEMPERATURE FOR STORAGE | -40…85 °C |
| RELATIVE HUMIDITY | 95 % without condensation |
| OPERATING ALTITUDE | <= 5000 m |
| UNIT TYPE OF PACKAGE 1 | PCE |
|---|---|
| NUMBER OF UNITS IN PACKAGE 1 | 1 |
| PACKAGE 1 HEIGHT | 16.3 cm |
| PACKAGE 1 WIDTH | 4.5 cm |
| PACKAGE 1 LENGTH | 31.2 cm |
| PACKAGE 1 WEIGHT | 520.0 g |
| UNIT TYPE OF PACKAGE 2 | S03 |
| NUMBER OF UNITS IN PACKAGE 2 | 7 |
| PACKAGE 2 HEIGHT | 30.0 cm |
| PACKAGE 2 WIDTH | 30.0 cm |
| PACKAGE 2 LENGTH | 40.0 cm |
| PACKAGE 2 WEIGHT | 4.2 kg |