Description
range of product | Modicon Quantum automation platform |
---|---|
product or component type | Unity processor |
clock frequency | 66 MHz |
---|---|
number of slots | 2 4 10 16 6 |
number of racks | 2 – local rack(s) |
number of distributed I/O station | 63 station(s) – 1 rack(s) – 3 Modbus Plus network(s) |
number of remote I/O station | 31 – 2 rack(s) per S908 remote I/O 0 – 0 rack(s) per ethernet remote I/O |
discrete I/O number | 31744 inputs, 31744 outputs – remote 8000 inputs, 8000 outputs – distributed – per network Modbus Plus Unlimited (26 slots max) – local |
analogue I/O number | 500 inputs, 500 outputs – distributed – per network Modbus Plus 1984 inputs,1984 outputs – S908 remote I/O Unlimited (26 slots max) – local |
application specific I/O | Serial link Counter High-speed interrupt inputs Accurate time stamping |
number of optional modules | 6 (Ethernet, Modbus, Modbus Plus, Profibus DP, Sy/Max) |
maximum number of connections | 2 AS-Interface – distributed 2 Modbus (RS232/485 Modbus/ASCII) 4 AS-Interface – remote 6 Ethernet TCP/IP – local 6 Modbus Plus – local 6 Profibus DP – local |
integrated connection type | 1 Modbus Plus with 2 Modbus with |
checks | Process control |
memory description | Internal RAM 1056 kB |
switch function | Key switch memory start/stop memory protection Slide switch communication port : ASCII/RTU/Memory |
application structure | 1 cyclic/periodic master task – 1 periodic fast task – 16 timer interrupt tasks – 64 I/O interrupt tasks – 64 interrupt tasks – No auxiliary task – |
execution time per instruction | 0.1…0.27 µs floating points 0.1…0.27 µs on fixed-point arithmetic 0.12…0.585 µs Boolean 0.12…0.585 µs on word |
number of instructions per ms | 1.86 Kinst/ms 100 % Boolean 2.49 Kinst/ms 65 % Boolean and 35 % numerical |
system overhead | 0.2 ms for fast task 1 ms for master task |
bus current requirement | 1800 mA |
local signalling | 1 LED (green) for communications are active on the Modbus Plus port (Modbus Plus) 1 LED (green) for communications are active on the Modbus port (Modbus) 1 LED (green) for CPU has been started and is solving logic (RUN) 1 LED (green) for CPU has passed the power-up diagnostic tests (READY) 1 LED (orange) for write-protected memory (memory port) 1 LED (red) for battery needs replacing or is not present (BAT LOW) 1 LED (red) for communications error on the Modbus Plus port (ERROR A) |
electrical connection | 1 female connector, connector type: SUB-D 9 for connecting to the Modbus Plus network 2 female connectors, connector type: SUB-D 9 for connecting to the Modbus bus |
product certifications | CSA CE UL |
---|---|
standards | HazLoc |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Weight | 607.0 g |
Package 1 Height | 4.5 cm |
Package 1 width | 15.5 cm |
Package 1 Length | 31.0 cm |
Unit Type of Package 2 | S03 |
Number of Units in Package 2 | 7 |
Package 2 Weight | 4.249 kg |
Package 2 Height | 30.0 cm |
Package 2 width | 30.0 cm |
Package 2 Length | 40.0 cm |