Description
range of product | Modicon Quantum automation platform |
---|---|
product or component type | Input/output analog module |
type of filter | Single pole low pass – 3 dB at 21 Hz +/- 20 % input circuit |
I/O modularity | 6 channels |
---|---|
addressing requirement | 2 output words 5 input words |
analogue input number | 4 |
analogue input type | Bipolar current +/- 20 mA – resolution: 15 bits DC Bipolar voltage +/- 10 V – resolution: 16 bits DC Bipolar voltage +/- 5 V – resolution: 15 bits DC Unipolar current 0…20 mA – resolution: 15 bits DC Unipolar offset current 4…20 mA – resolution: 14 bits DC Unipolar offset voltage 1…5 V – resolution: 14 bits DC Unipolar voltage 0…10 V – resolution: 16 bits DC Unipolar voltage 0…5 V – resolution: 15 bits DC |
absolute maximum input | +/- 25 mA current +/- 50 V voltage |
input impedance | > 10 MOhm voltage > 250 Ohm current |
offset | +/- 0.0014 % of full scale maximum/°C 0…60 °C input circuit |
gain shift | +/- 0.002 of full scale maximum 0…60 °C input circuit |
common mode rejection | > 80 dB 50/60 Hz input circuit |
analogue output number | 2 |
analogue output range | 4…20 mA |
analogue output resolution | 12 bits |
loop voltage | 0…60 V DC with external resistance output circuit 7…30 V DC output circuit |
maximum voltage drop | <30 V DC at 20 mA |
setting time | 900 µs to +/- 0.1 % of the final value output circuit |
external power requirement | 7…30 V output circuit |
absolute accuracy error | +/- 0.004 % of full scale at 0…60 °C output circuit +/- 0.007 %/°C of full scale maximum at 0…60 °C output circuit +/- 0.03 % at 25 °C input circuit +/- 0.05 % of full scale maximum at 25 °C input circuit +/- 0.20 % of full scale at 25 °C output circuit |
linearity | 2.4 % over and under range voltage 2.4 % over range, and – 9.6 % under range current Monotonic +/- 1 LSB input Monotonic +/- 1 LSB output |
update time | 15 ms output circuit 320 ms input circuit |
fault type | Open circuit input/output circuit Overtacking scale (unipolar) input circuit Status byte output circuit |
isolation between channels | 500 V AC for 1 minute 750 V DC for 1 minute |
isolation between channels and bus | 500 V AC for 1 minute 750 V DC for 1 minute |
isolation between input channel and output channel | 500 V for 1 minute 750 V for 1 minute |
marking | CE |
local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault 6 LEDs (green) for channel is turned on 6 LEDs (red) for channel fault |
bus current requirement | 350 mA |
module format | Standard |
net weight | 0.3 kg |
product certifications | FM Class 1 Division 2 C-Tick.1 |
---|---|
standards | UL 508 CSA C22.2 No 142 |
resistance to electromagnetic fields | 10 V/m 80…2000 MHz conforming to IEC 801-3 |
ambient air temperature for operation | 0…60 °C |
ambient air temperature for storage | -40…85 °C |
relative humidity | 95 % without condensation |
operating altitude | <= 5000 m |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Weight | 461.0 g |
Package 1 Height | 5.0 cm |
Package 1 width | 16.4 cm |
Package 1 Length | 31.0 cm |
Unit Type of Package 2 | S03 |
Number of Units in Package 2 | 7 |
Package 2 Weight | 3.62 kg |
Package 2 Height | 30.0 cm |
Package 2 width | 30.0 cm |
Package 2 Length | 40.0 cm |