Description
range of product | Modicon Quantum automation platform |
---|---|
product or component type | Analogue output module |
analogue output number | 8 |
---|---|
addressing requirement | 8 output words |
loop voltage | 6…30 V DC |
maximum voltage drop | <30 V 25 mA |
analogue output range | 0…20 mA 0…20000 counts 0…25 mA 0…25000 counts 4…20 mA 0…16000 counts 4…20 mA 0…4095 counts |
absolute accuracy error | +/- 0.2 % of full scale at 25 °C |
linearity | +/- 12 µA 4…20 mA 0…4095 counts +/- 4 µA 0…20 mA 0…20000 counts +/- 4 µA 0…25 mA 0…25000 counts +/- 4 µA 4…20 mA 0…16000 counts |
accuracy drift according to temperature | 0.004 % of full scale/°C typical 0.007 % of full scale/°C maximum |
isolation between channels and bus | 1780 V for 1 minute AC |
update time | 5 ms |
setting time | 3.2 ms to +/-0.1% of the final value 1.6 ms to 5% of the final value |
fault type | Open circuit 4…20 mA |
bus current requirement | 550 mA |
maximum power dissipation in W | 5 W |
external power requirement | 6…30 V |
marking | CE |
local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault 8 LEDs (green) for channel is turned on 8 LEDs (red) for channel fault |
module format | Standard |
net weight | 0.3 kg |
product certifications | CUL FM Class 1 Division 2 |
---|---|
standards | UL 508 CSA C22.2 No 142 |
resistance to electromagnetic fields | 10 V/m 80…2000 MHz conforming to IEC 801-3 |
ambient air temperature for operation | 0…60 °C |
ambient air temperature for storage | -40…85 °C |
relative humidity | 95 % without condensation |
operating altitude | <= 5000 m |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Weight | 460.0 g |
Package 1 Height | 5.0 cm |
Package 1 width | 16.5 cm |
Package 1 Length | 32.0 cm |
Unit Type of Package 2 | S03 |
Number of Units in Package 2 | 7 |
Package 2 Weight | 3.72 kg |
Package 2 Height | 30.0 cm |
Package 2 width | 30.0 cm |
Package 2 Length | 40.0 cm |