Description
| range | Enerlin’X |
|---|---|
| product name | Link |
| product or component type | Gateway |
| device short name | Link150 |
| device application | Gateway |
| external supply | External supply: 19.2…26.4 V DC, <500 mA |
| PoE | Power supply device PoE conforming to IEEE 802.3af |
| number of port | 2 |
| communication gateway | Ethernet/fieldbus |
| current consumption | 130 mA at 24 V DC via external supply (20 °C) 65 mA at 48 V DC via PoE (20 °C) |
|---|---|
| maximum power consumption in W | 15 W via PoE |
| communication network type | Ethernet, Ethernet Modbus TCP/IP daisy chain even/odd or none parity, at 10/100 Mbit/s Ethernet, PoE 15W (Power over Ethernet) even/odd or none parity, at 10/100 Mbit/s Ethernet, FTP even/odd or none parity, at 10/100 Mbit/s Ethernet, HTTP even/odd or none parity, at 10/100 Mbit/s Ethernet, SNMP even/odd or none parity, at 10/100 Mbit/s Ethernet, Modbus TCP/IP even/odd or none parity, at 10/100 Mbit/s RS232, Modbus RTU, JBUS, PowerLogic (SY/MAX) even/odd or none parity, at 2400, 4800, 9600, 19200 or 38400 bauds RS232, Modbus ASCII even/odd or none parity, at 2400, 4800, 9600, 19200, 38400, 56000 or 57600 bauds RS232, Modbus Serial line slave even/odd or none parity, at 2400, 4800, 9600, 19200 or 38400 bauds RS485, Modbus RTU, JBUS, PowerLogic (SY/MAX) even/odd or none parity, at 2400, 4800, 9600, 19200 or 38400 bauds RS485, Modbus ASCII even/odd or none parity, at 2400, 4800, 9600, 19200 or 38400 bauds RS485, Modbus Serial line slave even/odd or none parity, at 2400, 4800, 9600, 19200 or 38400 bauds |
| parity | Even/odd or none |
| communication port protocol | Ethernet Modbus TCP/IP daisy chain, insulation 6 kV Modbus TCP/IP, insulation 6 kV Modbus RTU, JBUS, PowerLogic (SY/MAX), master – 2 or 4 wires, insulation 2.5 kV Modbus ASCII, master – 2 or 4 wires, insulation 2.5 kV Modbus RTU and ASCII, slave – 2 or 4 wires, insulation 2.5 kV |
| communication port support | RJ45: Ethernet RJ45: RS232 RJ45: RS485 |
| number of inputs | 0 |
| number of outputs | 0 |
| connections – terminals | Power supply: screw terminal block (top) 0.2…1.5 mm² cable(s) rigid Power supply: screw terminal block (top) 0.2…1.5 mm² cable(s) flexible with cable end Power supply: screw terminal block (top) 0.2…1.5 mm² cable(s) flexible without cable end |
| tightening torque | Power supply: 0.3 N.m flat screwdriver 3 mm |
| wire stripping length | Power supply: 7 mm for top connector connection |
| mounting mode | Clip-on |
| mounting support | 35 mm DIN rail |
| product certifications | CULus FCC Class A CE RCM UL cUL |
| standards | IEC 60950-1 UL 61010-2-201 UL 61010-1 CSA C22.2 No 60950-1 AS/NZS 60950-1 UL 60950-1 IEC 61000-6-2 |
| depth | 72 mm |
| height | 105 mm |
| width | 71 mm |
| net weight | 175 g |
| web services | Web server |
| local signalling | LED: for Ethernet activity (ETH1) LED: for Ethernet activity (ETH2) LED: for module status LED: for network communication status (Net Status) LED: for communication (RS232) LED: for communication (RS485) |
| compatibility code | EGX150 |
| relative humidity | 5…95 % at 55 °C without condensation |
|---|---|
| IP degree of protection | IP40 (front panel (in enclosure)) IP30 (casing) IP20 (terminal block) |
| mechanical robustness | Vibrations in operation: 1 Gn, 5 Hz…150 Hz conforming to IEC 60068-2-6 Vibrations de-energized: 1 Gn, 5 Hz…150 Hz conforming to IEC 60068-2-6 Shocks in operation: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks de-energized: 15 Gn for 11 ms conforming to IEC 60068-2-27 Jolts de-energized: 100 jolts/axle, 15 Gn for 6 ms conforming to IEC 60068-2-29 Free fall resistance: 1.2 m |
| electromagnetic compatibility | Immunity for industrial environments conforming to EN 61000-6-2 Immunity for industrial environments conforming to CISPR 24 Conducted and radiated emissions conforming to FCC part 15 class B Conducted and radiated emissions conforming to EN 55022 Conducted and radiated emissions conforming to CISPR 22 Electrostatic discharge – test level: 8 kV air, 6 kV contact B conforming to EN 61000-4-2 Radiated RF fields – test level: 10 V/m, 80 MHz…1 GHz A conforming to EN 61000-4-3 Radiated RF fields – test level: 3 V/m, 1 MHz…3 GHz A conforming to EN 61000-4-3 Fast transients immunity test level 4 conforming to EN 61000-4-4 Fast transient bursts class 3 conforming to EN 61000-4-12 Surges – test level: level 4 B (1.2/50 µs) conforming to EN 61000-4-5 Conducted RF disturbances – test level: 10 V conforming to EN 61000-4-6 Conducted RF disturbances conforming to CISPR 11 Magnetic field at power frequency – test level: 30 A/m class 5 conforming to EN 61000-4-8 Voltage dips and interruptions immunity test – test level: 100 %, 20 ms B conforming to EN 61000-4-11 Voltage dips and interruptions immunity test – test level: 60 %, 200 ms B conforming to EN 61000-4-11 Voltage dips and interruptions immunity test – test level: 30 %, 500 ms conforming to EN 61000-4-11 |
| ambient air temperature for operation | -25…70 °C |
| ambient air temperature for storage | -40…85 °C |
| pollution degree | 2 |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Weight | 304.0 g |
| Package 1 Height | 9.0 cm |
| Package 1 width | 9.0 cm |
| Package 1 Length | 12.5 cm |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 192 |
| Package 2 Weight | 72.0 kg |
| Package 2 Height | 75.0 cm |
| Package 2 width | 60.0 cm |
| Package 2 Length | 80.0 cm |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 24 |
| Package 3 Weight | 8.01 kg |
| Package 3 Height | 30.0 cm |
| Package 3 width | 30.0 cm |
| Package 3 Length | 40.0 cm |